Description
ControlAir Type 590X 4 to 20 mA I/P transducer
ControlAir Type 590X converts a 4 to 20 mA current signal into proportional pneumatic outlet pressure. A standard ported Type 590X is distinct from the manifold-mount Type 590X configuration that connects through a common mounting face.
Key Product Details
- Supplier: ControlAir
- Manufacturer model: Type 590X
- Store SKU: Type 590X
- Product type: 4 to 20 mA I/P transducer
- Distinguishing details: 4 to 20 mA input; multiple calibrated output ranges
- Product category: IP Transducers
Type 590X operation
An open-loop, low-mass magnetic mechanism resists vibration and permits mounting in any orientation. Choose a factory-calibrated outlet span that matches the receiving pneumatic instrument.
Type 590X supply and mounting
A 3–15 psig outlet version is rated for a maximum 22 psig air supply, whereas the 3–27 and 6–30 psig versions allow up to 42 psig. Supply must also remain at least 5 psig above the selected output maximum. The ported instrument has a terminal-block electrical connection and can use a separately ordered DIN rail mounting kit. Its 1/8 inch NPT pneumatic ports differ from the common-face ports of the manifold configuration; select the interface before designing the panel or valve-positioner connections.
Technical specifications
Electrical input: 4–20 mA current loop
Available outlet spans: 3–15, 3–27 or 6–30 psig
Pneumatic connection: 1/8 inch NPT ported arrangement
Maximum supply: 22 psig for a 3–15 psig outlet; 42 psig for 3–27 and 6–30 psig outlets
Minimum supply: 5 psig above selected maximum outlet
Maximum flow capacity: 2.4 SCFM under manufacturer test conditions
Operating medium: clean, dry, oil-free air filtered to 40 microns
Control design: Open-loop low-mass magnetic conversion
Selection and use
For ControlAir Type 590X, choose the calibrated output range, electrical termination and any required approval by exact configured part number. FM and CSA details and optional ATEX/UKCA variants require the matching unit markings.
Connect a 4 to 20 mA instrument loop and clean regulated air. Route outlet pressure to the receiving valve positioner or actuator pilot; verify output at low and high electrical commands.
Due to the technical nature of this product, please contact our sales team on 01342 826488 or email info@aegroup.uk.com if you have any questions.
Lead Time
Product Availability
We work with a wide network of trusted manufacturers and suppliers to offer a comprehensive range of industrial components and systems. Many popular items are held in stock and available for prompt dispatch. These products are supplied directly from our UK facilities where possible to minimise lead times.
Order In and Made to Order Items
Some specialist products are not held as off the shelf stock. These items are ordered directly from the manufacturer and may be produced to order or configured for specific applications. As a result, lead times can be longer than standard stocked products, particularly for low volume or unique items. Lead times will vary depending on supplier schedules and production requirements.
Lead Times and Order Updates
For all order in products, we aim to provide clear lead time information at the point of order or shortly afterwards. Our team will keep you informed throughout the process and will advise if supplier lead times change. If you have a time critical requirement, we recommend contacting us before placing your order so we can confirm availability.
Delivery Charges
Additional delivery charges may apply to large orders, oversized items, palletised shipments, or deliveries outside the UK mainland including remote locations. Our sales team can confirm any applicable charges either before or after your order is placed to ensure full transparency.
Availability and Lead Time Enquiries
For the latest information on product availability and current lead times, please contact our team directly. We will confirm stock status, supplier lead times, and delivery expectations to support your ordering decision. You can email info@aegroup.uk.com or call +44 (0)1342 826488 to speak with a member of our team who can assist with your enquiry.
More Than Components
Experts you can trust. Technologies you can depend on.
Air Engineering Group is more than a component supplier. We operate as an engineering partner supporting customers from concept through to long term operation. Our role extends beyond product supply into system design, integration, build, installation, and lifecycle support. This approach allows us to solve complex technical challenges while improving reliability, efficiency, and operational assurance across demanding industrial environments.
Our OEM Fluid Technology Division focuses on engineered solutions for original equipment manufacturers. We support customers with design input, component selection, manifold assemblies, sub assemblies, and fully integrated pneumatic and fluid systems. Working closely with OEM teams, we help reduce complexity, improve performance, and accelerate development while maintaining consistency from prototype through to production.
The Compressed Air and Gas Division delivers complete compressed air and gas solutions for industrial and commercial applications. This includes system design, equipment supply, installation, commissioning, servicing, and ongoing maintenance. By taking responsibility for the full system, we help customers improve uptime, control energy use, and protect critical assets throughout their operational life.
Our Pneumatic and Fluid Product Division provides a comprehensive range of valves, actuators, regulators, filtration, fittings, and control components. Supported by in house technical expertise, this division ensures customers specify the correct products for their application while benefiting from reliable supply and informed engineering support. Together, these three divisions position us as a complete engineering solutions provider rather than a simple distributor.
Our approach to business is built around a clear customer first focus supported by engineering integrity and accountability. We take time to understand each application, operating environment, and performance requirement before recommending or designing a solution. This ensures customers receive systems and components that deliver reliability, efficiency, and long term value rather than short term fixes. Through clear communication, responsive support, and consistent technical standards, we build trusted partnerships that prioritise uptime, risk reduction, and operational confidence.
Speak to our engineering team by emailing info@aegroup.uk.com or call +44 (0)1342 826488 to speak with a member of our team who can assist with your enquiry.
Applications & Integrations
Applications
ControlAir Type 590X (SKU Type 590X) changes a current command into proportional instrument-air pressure where a compact, vibration-resistant I/P converter is useful. It can drive a valve positioner or pneumatic control element with an electrical process signal. A direct Type 590X uses individual supply and output connections, while the separately selected manifold version joins a common interface. Compared with a large enclosed I/P unit, the Type 590X provides a smaller field instrument suited to a modest output-flow requirement. A positioner with low air consumption is a realistic receiver for its proportional output. Direct mounting avoids the separate manifold interface of the 590X-1 version.
Integrations
Connect the specified current loop to the Type 590X terminals and clean air to its correctly identified supply port. Run the proportional air outlet to the receiving pneumatic device, and keep the exhaust and zero/span adjustment clear. Select the exact pressure range and permissible loop load from the full unit code, then test electrical input and actual outlet pressure together over several points. Its actual signal is a 4–20 mA current loop rather than a voltage command. Reserve DIN-rail or panel space for the selected mounting and verify that current increments create the expected pressure output. Keep signal wiring separate from pneumatic discharge during inspection.