Description
Product Overview
Parker 003-0875-900 is a Series 3 miniature inert liquid solenoid valve with 2 way normally closed operation, a 0.055 inch (1.40 mm) orifice, a vacuum to 100 psig (approximately 6.89 bar) operating range, 24 VDC coil and manifold mount. It combines a PEEK liquid body, PTFE and stainless steel wetted components with FKM seals.
The 1.40 mm orifice provides the highest pressure rating in the standard Series 3 ordering table. It suits circuits where a 100 psig rating takes priority over the larger orifice options.
Selection Differences
- Voltage selection: 003-0874-900 uses 12 VDC and 2.5 W rated power with the same function, orifice, seal build and liquid interface.
- Liquid interface: 003-0096-900 uses 1/16 inch (1.6 mm) ID tubing barbs with the same function, pressure rating, voltage and seal build.
- Seal and build selection: 003-0873-900 is the dedicated bleach-compatible FKM version with the same function, pressure rating, voltage and liquid interface.
Parker 003-0875-900 Technical Specifications
- Part number: 003-0875-900
- Function and construction: 2 Way Normally Closed; direct acting inert non-isolation liquid valve
- Operating pressure: Vacuum to 100 psig (approximately 6.89 bar)
- Orifice: 0.055 inch (1.40 mm)
- Liquid connections: Manifold mount
- Electrical supply: 24 VDC; 4.2 W rated power; 173 mA nominal current
- Coil resistance: 139 ohms, ±5% at 21.1 °C
- Electrical leads: 12 inch (304.8 mm), 26 AWG, PTFE insulated flying leads
- Body and wetted materials: PEEK body; PTFE and stainless steel wetted components; FKM seals
- Seal build: FKM standard version
- Operating environment: 4 to 66 °C (40 to 150 °F)
- Response and leakage: Less than 12 ms cycling; bubble-tight leak specification
- Proof pressure: 1.5 times rated pressure (150 psig)
- Filtration: 40 µm maximum recommended
- Nominal life: 10 million cycles, application dependent
- Internal volume: 208 µL, published family figure for the manifold interface
- Weight: 51 to 56 g, family range
- Power reduction: 8 VDC / 0.46 W hold after 25 ms at full rated voltage
- Compliance: RoHS compliant
Liquid and Electrical Integration
The liquid path is closed when the coil is de-energised and opens when energised. The design supports pressure or vacuum applied under or over the seat, using the appropriate port arrangement.
The standard FKM build supports compatible reagent, wash solution, saline and ink circuits. Parker rates FKM favourably for deionised water, isopropanol and saline in its abbreviated compatibility chart. Select the seal against the complete liquid formulation and operating conditions. The manifold interface routes liquid through the base of the valve. Match the manifold passages, seal support and port orientation to the selected valve drawing. Allow access for the lead wires and service removal.
Apply full 24 VDC for the initial 25 ms, then reduce to 8 VDC for approximately 0.46 W hold power. Validate the driver and switching behaviour in the intended circuit.
The ordering code identifies the valve with its standard flying leads. Select suitable mounting hardware, a matching liquid manifold and an electrical driver for the complete equipment assembly.
OEM Fluid Control Support
Air Engineering Group Ltd can supply Parker 003-0875-900 as an individual valve or support integration into an OEM liquid control assembly. Support can include application review, component selection, manifold and circuit design, prototyping, assembly, functional testing and repeat manufacture against agreed requirements.
Due to the technical nature of this product, please contact our sales team on 01342 826488 or email info@aegroup.uk.com if you have any questions.
Brand
Parker
Parker Hannifin develops precision fluid control valves for OEM equipment that requires compact dimensions, reliable switching and efficient electrical control. Its extensive portfolio includes miniature pneumatic solenoid valves, proportional flow valves, cartridge valves and diaphragm isolation valves for controlling gases and liquids. Available configurations support pressure and vacuum switching, proportional flow control and media isolation, with options for manifold, PCB and tube integration.
Parker valve technologies are used within respiratory equipment, anaesthesia systems, patient monitoring devices, diagnostic instruments, laboratory automation and other medical or life science equipment. AEG helps OEM customers select the appropriate valve function, pressure range, flow capacity, voltage, materials, elastomer and connection method, before integrating the selected components into custom manifolds, pneumatic assemblies or complete fluid control solutions.
Lead Time
Product Availability
We work with a wide network of trusted manufacturers and suppliers to offer a comprehensive range of industrial components and systems. Many popular items are held in stock and available for prompt dispatch. These products are supplied directly from our UK facilities where possible to minimise lead times.
Order In and Made to Order Items
Some specialist products are not held as off the shelf stock. These items are ordered directly from the manufacturer and may be produced to order or configured for specific applications. As a result, lead times can be longer than standard stocked products, particularly for low volume or unique items. Lead times will vary depending on supplier schedules and production requirements.
Lead Times and Order Updates
For all order in products, we aim to provide clear lead time information at the point of order or shortly afterwards. Our team will keep you informed throughout the process and will advise if supplier lead times change. If you have a time critical requirement, we recommend contacting us before placing your order so we can confirm availability.
Delivery Charges
Additional delivery charges may apply to large orders, oversized items, palletised shipments, or deliveries outside the UK mainland including remote locations. Our sales team can confirm any applicable charges either before or after your order is placed to ensure full transparency.
Availability and Lead Time Enquiries
For the latest information on product availability and current lead times, please contact our team directly. We will confirm stock status, supplier lead times, and delivery expectations to support your ordering decision. You can email info@aegroup.uk.com or call +44 (0)1342 826488 to speak with a member of our team who can assist with your enquiry.
More Than Components
Experts you can trust. Technologies you can depend on.
Air Engineering Group is more than a component supplier. We operate as an engineering partner supporting customers from concept through to long term operation. Our role extends beyond product supply into system design, integration, build, installation, and lifecycle support. This approach allows us to solve complex technical challenges while improving reliability, efficiency, and operational assurance across demanding industrial environments.
Our OEM Fluid Technology Division focuses on engineered solutions for original equipment manufacturers. We support customers with design input, component selection, manifold assemblies, sub assemblies, and fully integrated pneumatic and fluid systems. Working closely with OEM teams, we help reduce complexity, improve performance, and accelerate development while maintaining consistency from prototype through to production.
The Compressed Air and Gas Division delivers complete compressed air and gas solutions for industrial and commercial applications. This includes system design, equipment supply, installation, commissioning, servicing, and ongoing maintenance. By taking responsibility for the full system, we help customers improve uptime, control energy use, and protect critical assets throughout their operational life.
Our Pneumatic and Fluid Product Division provides a comprehensive range of valves, actuators, regulators, filtration, fittings, and control components. Supported by in house technical expertise, this division ensures customers specify the correct products for their application while benefiting from reliable supply and informed engineering support. Together, these three divisions position us as a complete engineering solutions provider rather than a simple distributor.
Our approach to business is built around a clear customer first focus supported by engineering integrity and accountability. We take time to understand each application, operating environment, and performance requirement before recommending or designing a solution. This ensures customers receive systems and components that deliver reliability, efficiency, and long term value rather than short term fixes. Through clear communication, responsive support, and consistent technical standards, we build trusted partnerships that prioritise uptime, risk reduction, and operational confidence.
Speak to our engineering team by emailing info@aegroup.uk.com or call +44 (0)1342 826488 to speak with a member of our team who can assist with your enquiry.
Applications & Integrations
Applications & Integration
Parker 003-0875-900 supports reagent shut-off, wash solution delivery and controlled waste removal. Its 2 way normally closed function, 1.40 mm orifice and 100 psig limit define its place in the circuit. The 1.40 mm orifice provides the highest pressure rating in the standard Series 3 ordering table. It suits circuits where a 100 psig rating takes priority over the larger orifice options.
Liquid Compatibility
The standard FKM build supports compatible reagent, wash solution, saline and ink circuits. Parker rates FKM favourably for deionised water, isopropanol and saline in its abbreviated compatibility chart. Select the seal against the complete liquid formulation and operating conditions.
Integration Guidance
The manifold interface routes liquid through the base of the valve. Match the manifold passages, seal support and port orientation to the selected valve drawing. Allow access for the lead wires and service removal. The liquid path is closed when the coil is de-energised and opens when energised. The design supports pressure or vacuum applied under or over the seat, using the appropriate port arrangement.
Provide a 24 VDC driver suitable for 4.2 W rated power and 173 mA nominal current. Apply full 24 VDC for the initial 25 ms, then reduce to 8 VDC for approximately 0.46 W hold power. Validate the driver and switching behaviour in the intended circuit. Size the liquid circuit for the required flow, viscosity and differential pressure, with filtration of 40 µm maximum and an operating environment of 4 to 66 °C.